Fire alarm control panel 2 zone Zeta, English
The Infinity 8 control panel is housed in the most attractive, newly designed, flame-resistant ABS enclosure, using a switch-mode power supply. It has a fully removable front cover that improves ease of access to cable installations. The Infinity 8 p more information
SAR 1,319.20
+
Earn loyalty points with this purchase
Rewardsproduct sku
Weight
share product
The Infinity 8 control panel is housed in the most attractive, newly designed, flame-resistant ABS enclosure, using a switch-mode power supply. It has a fully removable front cover that improves ease of access to cable installations. The Infinity 8 panel can also be ordered with a metal back box that makes it easy to fit up to 7ah batteries inside the panel's chassis. To order this version, add "/M" to the end of the model number (i.e. IN1/M, IN2/M, etc.).
Features
Password access - eliminates the problem of lost keys One man testing facility Disabling facility for zones and audio devices Space for up to 3 amp batteries Sounder delay option 4 sounder circuits (IN4, IN6 and IN8) 3 and/or 4 sounder circuits can be configured as 24V Aux input Meets supplies All requirements of the latest EN54 Part 2 and Part 4
Model IN2
Part No. 37-650
Mains voltage 230 VAC +10% / -15% at 50/60 Hz
System voltage 24V DC (nominal)
Zone voltage 21V DC (nominal)
Sounder alarm output 2 x 150mA @ 24V DC 4 x 150mA @ 24V DC
Fault Relay 1 x Free Relay Volt, SELV @ 1A Max
Zone capacity is 32 devices per zone
Remotely operate the audio device via the N/O contact connected to change the category
Sounder activation delay from 0 to 10 minutes in 1-minute increments
Diode line end region 1N4002 (cathode bar to +ve region)
Sounder end of line resistor 10K
Charger voltage is 27.6 volts
Battery cut-off Battery voltage is less than 20V
The internal resistance limit of the battery is 0.9 ohms
Case size 371 x 302 x 93 (mm)
Weight 3 kg (excluding batteries)
Maximum battery space is 2 x 3.4Ah, 12V DC sealed lead acid battery